Aerial Bunch Cable with lighting Conductor of 16 sq. mm

 

Aerial Bunch Cable : 1.1 KV grade Stranded & Compacted Aluminium Phase Conductor, and
Stranded Messenger Conductor with all Aluminium Alloy, Phase Conductor is insulated with XLPE
Compound, Messenger is either insulated or bare with lighting Conductor of 16 mm
as per Specification IS : 14255 – 1995 upto the latest amendment.
Sl. No Description
and type of table
Number of Wires Thikness of XLPE Insulation Approx overall Diameter Approx weight of cable Breaking load of messenger Maximum D.C. resistance Ohms / Km AC CurrentAmps
Phase Messenger Phase Messenger
mm mm mm Kg/Km KN(min) Phase Messenger In air at 40ÂșC
With insulated messenger conductor
1 3C x 16 mm2 + 25 mm2(insulated)+16 mm2 7 7 1.20 1.20 23.5 369 7.0 1.910 1.380 62
2 3C x 25 mm2 + 25 mm2(insulated)+16 mm2 7 7 1.20 1.20 25.0 457 7.0 1.200 1.380 82
3 3C x 35 mm2 + 25 mm2(insulated)+16 mm2 7 7 1.20 1.20 27.5 554 7.0 0.868 1.380 103
4 3C x 35 mm2 + 35 mm2(insulated)+16 mm2 7 7 1.20 1.20 28.4 586 10.1 0.868 0.986 103
5 3C x 50 mm2 + 35 mm2(insulated)+16 mm2 7 7 1.50 1.20 32.5 760 10.1 0.641 0.986 127
6 3C x 70 mm2 +50 mm2(insulated)+16 mm2 7 7 1.50 1.50 37.5 1007 14.0 0.443 0.689 154
7 3C x 70 mm2 + 70 mm2(insulated)+16 mm2 7 7 1.50 1.50 39.5 1070 19.7 0.443 0.492 154
8 3C x 95 mm2 + 70 mm2(insulated)+16 mm2 19 7 1.50 1.50 42.5 1304 19.7 0.320 0.492 188
9 3C x 120 mm2 + 70 mm2(insulated)+16 mm2 19 7 1.60 1.50 46.8 1550 19.7 0.253 0.492 218
10 3C x 150 mm2 + 70 mm2(insulated)+16 mm2 19 7 1.80 1.50 50.5 1860 19.7 0.206 0.492 218
With insulated messenger conductor
1 3C x 16 mm2 + 25 mm2(insulated)+16 mm2 7 7 1.20 N.A* 19.5 340 7.0 1.910 1.380 62
2 3C x 25 mm2 + 25 mm2(insulated)+16 mm2 7 7 1.20 -do- 20.5 429 7.0 1.200 1.380 82
3 3C x 35 mm2 + 25 mm2(insulated)+16 mm2 7 7 1.20 -do- 23.5 526 7.0 0.868 1.380 103
4 3C x 35 mm2 + 35 mm2(insulated)+16 mm2 7 7 1.20 -do- 25.0 553 10.1 0.868 0.986 103
5 3C x 50 mm2 + 35 mm2(insulated)+16 mm2 7 7 1.50 -do- 26.8 727 10.1 0.641 0.986 127
6 3C x 70 mm2 +50 mm2(insulated)+16 mm2 7 7 1.50 -do- 31.5 958 14.0 0.443 0.689 154
7 3C x 70 mm2 + 70mm2(insulated)+16 mm2 7 7 1.50 -do- 34.5 1013 19.7 0.443 0.492 154
8 3C x 95 mm2 + 70 mm2(insulated)+16 mm2 19 7 1.50 -do- 37.0 1248 19.7 0.320 0.492 188
9 3C x 120 mm2 + 70 mm2(insulated)+16 mm2 19 7 1.60 -do- 39.0 1493 19.7 0.253 0.492 218
10 3C x 150 mm2 + 70 mm2(insulated)+16 mm2 19 7 1.80 -do- 40.0 1803 19.7 0.206 0.492 248